Ilyas,

 I generally use a value that is 5 times the default. As Toni correctly pointed out the default accounts only for the thermal capacitance of the air contained in the thermal zone.

kind regards,

 David



On 01/25/2017 16:31, Ilyas KHELIFA KERFAH wrote:
Hello.
I have a question about the capacitance of TRNSYS zones.
I see in the TRNBUILD that the value by default to calculate the capacitance (volume of the pieces * 1.2). it's logic ?. thank you.



-- 
***************************
David BRADLEY