Dear Qi Cheng, for thick walls you need to increase the time base, the wall transfer functions relates to this value. (See 5.4.1.4. and 5.4.1.5. for further information). The value should be in the range of 0.5 for light walls and 3 for very heavy walls. Regards. __________________________________________________________________________________________________ Jochen Lam TRNSYS Software Team
Curiestraße 2 70563 Stuttgart Fax: +49 711 67976-11 Web: www.trnsys.de
Von: trnsys-users-bounces@cae.wisc.edu [mailto:trnsys-users-bounces@cae.wisc.edu]
Im Auftrag von Cheng Qi Dear Madam/Sir, Sorry to disturb you. I want to construct a wall in Type 56 which consists of 1m heavyweight concrete and 2.5m stone aggregate concrete. But in Type 56, the thickness of wall cannot be exceed 1m. If possible, could you give me some suggestion. Regards Qi Cheng Department of Building Service Engineering Hong Kong Polytechnic University Kowloon, Hong Kong |