Dear Manuelle, First, sorry for the last mail which was not complete. You can have different TIME BASE and TIME STEP in your model. For exemple, you may have a 1h time step in STUDIO with a 4h time base in TRNBUILD. The time base in TRNBUILD allows you to simulate massive walls (see manual or archive TRNSYS mailing list if you want more explanation). The only rule to follow is that TRNSYS simulation time step cannot be greater than TRNBUILD time base. Concerning the error you meet, I think that it comes from Type 16 "Time of last data read" and "time of next data read" input definition. These inputs may be connected to Type 9 "Time of last data read" and "time of next data read" outputs. Best regards, Adrien Manuel Dalle Nogare a écrit :
--
|