[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] TRNbuild problem



Dear Guillaume,

Your error is a classical one when using very thin walls or very thick walls. You just have to change the timebase in the outputs window in trnbuild. For thin walls, timebase should be less than 1 and bigger than 1 for thick walls. In my projects, I often use thick walls and I often define timebase = 3, 4 or 5 h.

Kind Regards,
Christophe.

At 21:20 31/01/2006, David Bradley wrote:
Guillaume,
When TRNBuild generates the Type56 files, it places the .inf, .bld, and .trn files all in the same location as the .bui file. If you aren't getting an .inf file when you save your .bui file, I would suggest that you send the .bui to your distributor to see if they can find the problem.

As a side note, very thin walls as well as very thick walls can sometimes cause problems in generating the Type56 files. Interior wood doors or steel garage doors are often the offending walls.

Kind regards,
  David


At 08:06 1/31/2006, Guillaume Renault wrote:
Hi everybody,
I have defined my own walls, by using only layers already existing, saved the walls in the user.lib. When I want to save the project, an error message appears, which says that I have to check the layer definition (thickness, ratio of conductivity/ density) and to check the INF-File for further information.

I checked the BUI file opened with a text reader, and I've found nothing wrong.
All of the wall's thickness are less than 1 meter !

Could someone tell me where is located the INF-File.

Thanks in advance,

_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@engr.wisc.edu
https://www.cae.wisc.edu/mailman/listinfo/trnsys-users

****************************************************************************************
Thermal Energy System Specialists (TESS), LLC
David BRADLEY                           2916 Marketplace Drive - Suite 104
Partner                                        Madison, WI 53719
Phone: (608) 274-2577 USA
Fax: (608) 278-1475
E-mail: bradley@tess-inc.com
Web Pages:  http://www.tess-inc.com     and      http://www.trnsys.com

"Providing software solutions for today's energy engineering projects"
****************************************************************************************


_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@engr.wisc.edu
https://www.cae.wisc.edu/mailman/listinfo/trnsys-users

===========================
ENERTECH
F-26160 FELINES SUR RIMANDOULE
tel-fax : 04 75 90 18 54
Email : sidler@club-internet.fr
Web  : http://sidler.club.fr
================================