Dear Trnsys users,
I want to simulate a system of building.
I
have the electrical consumption loads = Pload_electricity (Watt) taken from the Energy
Plus data.
1 - Using
the Equation Block, pre-defined in the examples, PVT,
Pload = peak load * 3, 6 * Fload [kJ / h]
The Fload = fractioned profile is then passed to the equation block, But ... I put the power values in W, taken hourly from the file, (3.6 corrections to the conversion factor to obtain the power in kJ / h).
If I don't use the fractional power value, Fload (Type 14), can I just get the Power load, without using the peak load, Pload = 3.6 * Power Load (Watt) [kJ / h]?
Likewise, I can adapt to the consumption profile of DHW. I do not want to put the fractional value in type 14 ?
The Trnsys example, SDHW, in the definition in the equation block:
“mdDHW = DHWProfile * 200“. I can replace the data from Type 14 (which were in fractions), by water consumption profile values in Liters / day / person? This is because I have several houses with very different consumption, making no sense to multiply by the total consumption of the houses.