Hey Arne,
the balance NTypes 901 – 908 are defined like the other outputs but in contrast to the other ones they don’t return a value. If they are defined a balance output files are printed in the directory of the Trnsys input file *.d18/dck.
You can define them in the output manager of TRNBuild.
In case you do not want to open TRNBuild. You can add the balance outputs in your *.b18/*.bui file like:
AIRNODES = YOUR_AIRNODE
NTYPES = 905 : BAL_5 - energy balance for a sum of zones
best,
Christoph
Von: TRNSYS-users <trnsys-users-bounces@lists.onebuilding.org> im Auftrag von Arne Hübner via TRNSYS-users <trnsys-users@lists.onebuilding.org>
Gesendet: Montag, 5. August 2019 11:47 An: trnsys-users@lists.onebuilding.org <trnsys-users@lists.onebuilding.org> Cc: Arne Hübner <arne.nils.huebner@gmail.com> Betreff: [TRNSYS-users] Energy_TOT.BAL
Hello TRNSYS-Users,
I simulated the TRNSYS Example Multizone Building from the Documentation 06-MultizoneBuilding.pdf. Now i want to see the Energy balance of that building with the Energy_TOT.Bal file. It says in the documentation to generate this file you have to select NTYPE 905 in Output Manager in SimulationStudio. But is there also a way to do that in the DECK file? I cant find a solution. Please find attached the files I used for the simulation. Thank you!
Arne Huebner Gesendet von Mail für Windows 10
|