Re: [TRNSYS-users] type 56 and active layers



Olivier,

  I don't think that Type56 has outputs for the outlet mass flow rate from an active layer. It does, of course, have outputs for the outlet temperature. However, since the inlet and outlet mass flow to/from the active layer are equal you can just pass the mass flow rate directly from collector to tank (bypassing the house) while the temperature into the tank will come from the house.

kind regards,

 David


On 02/25/2019 12:09, Le Talave via TRNSYS-users wrote:

Dear Trnsys community,

I try to simulate a house heated by sensors and solar collectors. I did a type 56 of the house and 5 active layers simulating heated walls. The house and collectors are each connected to a pump and a solar tank with 2 HX, everything works well.
I want to put the collectors and the house in series (coll-> house-> tank-> coll). Now, an error occurs because there is no flow information between the house and the tank. When I created active layers, I linked their temperature / flow to 2 inputs connected to a pump in Trnsys. But is it possible to create 2 temp/flow outputs to be able to connect the house to the tank?

Thank you very much for your advice

Best regards,

Olivier


_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@lists.onebuilding.org
http://lists.onebuilding.org/listinfo.cgi/trnsys-users-onebuilding.org
-- 
***************************
David BRADLEY
Principal
Thermal Energy Systems Specialists, LLC
3 North Pinckney Street - suite 202
Madison, WI  53703 USA

P:+1.608.274.2577
F:+1.608.278.1475
d.bradley@tess-inc.com

http://www.tess-inc.com
http://www.trnsys.com