Re: [TRNSYS-users] need help for trnflow error



Dear Van Long LE,

 

All  airnodes of a Trnflow network have to be connected by links.

There is missing a link between Zone_E5 and zone_F5.

 

In addition, for TRNFlow you need to define the “air inlet” AND “air outlet”. The outlets is missing.

 

Kind regards,

Christoph

 

__________________________________________________________________________________________________

 

Transsolar Energietechnik GmbH

Curiestraße 2

70563 Stuttgart

http://www.transsolar.com

Transsolar: KlimaEngineering- Technologien für energieeffizientes Bauen und Nutzerkomfort in Gebäuden

Stuttgart – München – New York – Paris

Geschäftsführer :Diplom-Ingenieur Matthias Schuler, Diplom-Ingenieur Thomas Auer, Diplom-Physiker Stefan Holst, Diplom-Betriebswirt Dieter Schnelle

Eingetragen beim Amtsgericht Stuttgart HRB 23347,

Steuernummer: 99073/00911,USt-IdNr.: DE 152272639

 

The simulation project you have sent will be stored on the local servers of Transsolar Energietechnik GmbH for the duration of the project support. Our employees are obliged by us to confidentiality. After this period, all project-related data is deleted.

 

The storage of your personal e-mail and other contact information is based on the mutual interest in the execution of this traffic and on a mutual business contact. If you have any questions, please contact our data protection officer at privacy@transsolar.com. Our privacy policy can be found here.

 

Von: TRNSYS-users <trnsys-users-bounces@lists.onebuilding.org> Im Auftrag von Long Le-Van via TRNSYS-users
Gesendet: Freitag, 28. September 2018 08:32
An: trnsys-users@lists.onebuilding.org; trnsys-users-request@lists.onebuilding.org
Cc: Long Le-Van <long.le-van@outlook.com>
Betreff: [TRNSYS-users] need help for trnflow error

 

Dears,

 

Could you please tell me why I cannot create the airflow network like below for my two-zones building

 

Indeed, I received the following error

 

 

Thank you very much for your help!

 

-----------

Van Long LE

Research Engineer

Energy & Building

 

Cenaero ASBL

Your trustworthy R&T partner

in modeling and numerical simulation

 

Tel.: +32 71 910 993

Fax: +32 71 910 931

 

Cenaero Headquarters

Rue des Frères Wright, 29

6041 Gosselies

Belgium

 

Visit our web site: www.cenaero.be

 

+-+-+- www.cenaero.be/disclaimer +-+-+-

 

Please consider the environment before printing this e-mail.