Francesca, Instead of defining a VENTILATION type that has inputs for the mass flow rate, air temperature and air humidity in TRNBuild you will define an active layer in TRNBuild and you will indicate that the mass flow rate and temperature of liquid entering the active layer are inputs to Type56. kind regards, David
On 03/28/2017 05:20, francesca lorusso
via TRNSYS-users wrote: