Avishek,
TRNSYS does not contain models of the component parts of an
absorption chiller. Its model of an absorption chiller is a
performance map that gives COP and capacity as a function of the
current inlet conditions of the chilled water, cooling water, and
hot water streams. The TESS HVAC and CoGen libraries contain similar
performance map models for single and double effect steam and direct
fired machines. In order to make a model of an absorption chiller
from first principals, you would have to write models of those
component pieces yourself using a Fortran compiler based on the
information available in the 07-Programmer's Guide manual
Regards,
David
On 3/12/2015 05:09, avishek ray wrote:
Hi,
i want to model the individual system components
like generator, absorber etc with TRNSYS based on the first
principle model ie by use of mass and energy balance
equations. I want to determine the specification of the
individual components. Pl guide me how it can be possible to
design it. i am urgently requiring it
Avishek Ray
Research Fellow and Teaching
Assistant
Department of Energy Management
Indian Institute Of Social Welfare and Business Management;
Kolkata-700073
M:9038707191
_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@lists.onebuilding.org
http://lists.onebuilding.org/listinfo.cgi/trnsys-users-onebuilding.org
--
***************************
David BRADLEY
Principal
Thermal Energy Systems Specialists, LLC
22 North Carroll Street - suite 370
Madison, WI 53703 USA
P:+1.608.274.2577
F:+1.608.278.1475
d.bradley@tess-inc.com
http://www.tess-inc.com
http://www.trnsys.com