On Jan 28, 2015, at 5:35 AM, Ole Nienaber <olenienaber@web.de> wrote:
Dear All,
I'm new here.
I have a problem with the cooling demand of a building zone.
I use the Cooling Type Manager to regulate my maximum temperature (24°c) in the zone. Also I use a schedule, because cooling isn't ON all the time.
So my formula for the Cooling Type Manager is: 24*SCHED+0. And here is the problem. If my schedule is OFF (=0), than, of course, the cooling cools down my room temperature on 0°C. But I just want control, that the room temperature never increase over 24°C. Is there another way I could do it?
Thanks a lot and I hope you all understand the problem.
Greetings,
Ole
_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@lists.onebuilding.org
http://lists.onebuilding.org/listinfo.cgi/trnsys-users-onebuilding.org