[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] Relevant outputs for validation of my building model



Hi Pauline,

I think you may check B4_QTRANS.
You can also have a look to NTYPE27, QUA output : Static UA transmission losses of air node with stationary U-values. Be careful, this output is evaluated with steady transmission of walls and windows without capacitance effect (check mutlizone help for more precision p5-27).
Otherwise, you may have a look to "summary.bal" file and eventualy "energy_zone.bal" if you select BAL_4 output (in balances) to have a complete
summary of each thermal zone

Best regards
 
Je serai en congé du 20/12/13 au 02/01/14 inclus
 
Logo_ITF
Adrien JEZEQUEL
Simulation Dynamique - Calculs numériques

62 rue du Bolliet
73230 SAINT-ALBAN-LEYSSE
Tél : +33(0) 479 750 029
Fax : +33(0) 479 852 122
a.jezequel@itf.biz
www.itf.biz
Feuille
Le 13/12/2013 15:48, Pauline GELIN a écrit :

Hi,

 

With aberrant results, I want to study all the possible gains and losses in an room of ​​ my building. Among all feasible outputs I selected the following: QINF (for infiltration), QVENT (for ventilation), QGCONV (for internal gains, only convective) B4_QSOL (for solar gains), but I cannot find one for static Losses from walls. Which would you advise me? In addition, those whom I have chosen are the ones most relevant?

 

Thanks a lot in advance for your help.

 

Best regards,

 

Pauline GELIN

Ingénieur Conception environnementale

 

cid:image004.jpg@01CE062A.F4C2C000

 

cid:image006.jpg@01CE062A.F4C2C000

10 avenue des canuts

69120 VAULX EN VELIN

T : 04.37.45.33.33 

 

Ligne directe : 04.37.45.33.47

 

www.katene.coop

www.quadriplus-groupe.com

www.woopa.coop



_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu