[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] Problem with Dry Fluid Cooler (type 511)



Thank you very much Tim. It’s working.

 

Best regards,

 

Max

 

Maxence BUREAU
Ingénieur de Recherche
Qualité d'Air Intérieur
______________________________________________________________________

Cofely


Centre de recherche Cylergie
L'Orée d'Ecully - Bât. C - Chemin de la Forestière
69130 - ECULLY
tel.
+33472860934 - fax +33478433959
Mob. +33637613217
mailto:maxence.bureau@cofely-gdfsuez.com
www.cofely-gdfsuez.fr

Before printing, think about the environment / Avant d'imprimer, pensez à l'environnement

 

De : trnsys-users-bounces@cae.wisc.edu [mailto:trnsys-users-bounces@cae.wisc.edu] De la part de mcdowell@tess-inc.com
Envoyé : lundi 15 avril 2013 17:20
À : TRNSYS users mailing list at the Solar Energy Lab, UW-Madison
Objet : Re: [TRNSYS-users] Problem with Dry Fluid Cooler (type 511)

 

My apologies, 20C for the design ambient air temperature works.

Regards,

Tim

---
Timothy P. McDowell
Executive Vice President
Thermal Energy System Specialists, LLC
22 N Carroll St, Suite 370
Madison, WI 53703
608-274-2577

On 2013-04-15 02:44, maxence.bureau@cofely-gdfsuez.com wrote:

Hello,

 

Thank you for your answer Timothy,

I try to change the design ambient air temperature to 26.67, but it isn’t run (all other design parameters have their default value). Maybe I forget something, but I don’t know what.

 

Regards,

 

Maxence BUREAU
Ingénieur de Recherche
Qualité d'Air Intérieur
______________________________________________________________________

Cofely


Centre de recherche Cylergie
L'Orée d'Ecully - Bât. C - Chemin de la Forestière
69130 - ECULLY
tel. +33472860934 - fax +33478433959
Mob. +33637613217
mailto:maxence.bureau@cofely-gdfsuez.com
www.cofely-gdfsuez.fr

Before printing, think about the environment / Avant d'imprimer, pensez à l'environnement

 

De : trnsys-users-bounces@cae.wisc.edu [mailto:trnsys-users-bounces@cae.wisc.edu] De la part de mcdowell@tess-inc.com
Envoyé : jeudi 11 avril 2013 21:36
À : TRNSYS users mailing list at the Solar Energy Lab, UW-Madison
Objet : Re: [TRNSYS-users] Problem with Dry Fluid Cooler (type 511)

 

Maxence -

You are correct, there is a problem with the default values in the Type511 Proforma. If you change the Design Ambient Air Temperature to 26.67 C it should run.

Regards,

Tim

---
Timothy P. McDowell
Executive Vice President
Thermal Energy System Specialists, LLC
22 N Carroll St, Suite 370
Madison, WI 53703
608-274-2577

On 2013-04-10 03:20, maxence.bureau@cofely-gdfsuez.com wrote:

Hello,

 

I would like to use a type 511 (HVAC Library (TESS) – Dry Fluid Cooler), but it doesn't work.

 

When the value of input 2 (fluid flow rate) is higher than 0, the simulation doesn’t work and an error message appear (“TRNSYS errors : one error was found in the deck…”).

 

I have this error message in "list file" :

"*** Fatal Error at time   :         0.125000

    Generated by Unit     :    10

    Generated by Type     :   511

    Message               : The dry cooler model was unable to correctly calculate the number of transfer units (NTU) for the design condition.  Please check the design conditions carefully."

 

I tested the type with the defaults design conditions, but it was the same error message. I think there is a problem with input 2.

 

Please find attached my “.tpf” file.

Thank you for your help.

 

Sincerely,

 

Maxence BUREAU
Ingénieur de Recherche
______________________________________________________________________


Centre de recherche Cylergie
L'Orée d'Ecully - Bât. C - Chemin de la Forestière
69130 - ECULLY
tel. +33472860980 - fax +33478433959
mailto:maxence.bureau@cofely-gdfsuez.com
www.cofely-gdfsuez.fr

Before printing, think about the environment / Avant d'imprimer, pensez à l'environnement

 


Before printing, think about the environment / Avant d'imprimer, pensez a l'environnement

GDF SUEZ Mail Disclaimer: http://www.gdfsuez.com/disclaimer/disclaimer-fr.html

 


Before printing, think about the environment / Avant d'imprimer, pensez a l'environnement

GDF SUEZ Mail Disclaimer: http://www.gdfsuez.com/disclaimer/disclaimer-fr.html