[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] Hybrid dessicant dehumidifier



I am wondering if some one has made a TRNSYS component for this
thing, or if there is a way to model it with existing ones.  The
DryCool HD dessicant dehumidifier by Munters.  See screenshot below
from the manual.

You can use one of the available air-source heat pump models and then direct the outlet air streams from both sides of this model across a desiccant coil model. I've done it on a few projects and it works well provided you can get enough catalog data to create the required heat pump data files.

Jeff


---
Jeff Thornton
President - TESS LLC
22 N. Carroll Street, Madison WI USA 53703
Office: (608) 274-2577  Fax: (608) 278-1475
www.tess-inc.com