Re: [TRNSYS-users] Thermal storage tank (Type4a)



Sleiman,
  With Type4, the question about how many nodes there are in the tank must be answered on the parameter, the output, and on the derivative tabs. Be careful as the output tab asks you to tell it how many nodes there are besides the top and bottom nodes.
Regards,
 David


On 11/28/2012 04:10, Farah, Sleiman - farsy019 wrote:

Dear TRNSYS users,

 

I have a project (TRNSYS 16) with thermal storage tank (Type4a) using “5” nodes. Whenever I use the “Update project” in the “Edit” menu and run the simulation, I get an error message. However, I found by chance that if I change the number of nodes of the storage tank to “1” node and then change the number again to “5” the simulation runs normally.

I wonder what would be the cause of this error.

 

Regards,

 

Sleiman

 

 

 

 