Sascha, this data set was
generated without spectral data at time where a 1-band window model existed in
TRNSYS only. Type 56 includes now
2-band model and old window IDs can produce this error due to the missing
spectral data. The window ID remained in
the library for backwards compatibility. The best solution is to select
a different window. Regards, Marion Dipl.-Ing.
Geschäftsführer:
Dipl.Ing. Matthias Schuler, Dipl.Ing. Von: Heinze
[mailto:heinze@ingweber.de] Dear
TRNSYS-Users, i
have question about the window data in Trnbuild. I used a glazing from the
WinID-Lib and i get 2 warning messages in the List-File: A Message
: winlib reader: Incorrect visual transmission values encountered in
Window-ID 4101. for an angle
of 0 °. Incorrect value
0.625 will be limited to the possible physically maximum 0.575!
Please check your window data! B Message
: winlib reader: incorrect selectivity of visual+solar transmission
caused a negative value for nonvisual Transmission Tra_ang_nonvis = -0.044 for
Window-ID 4101 at an angle
of 0 ° Tra_ang_nonvis is set to 0 for this angle Does
anybody know how to fix this ? Best
regards Sascha
Heinze |