Dear Devin, Your active layer have to be placed between two layers. As written in the manual, "the thickness of both layers adjacent to active layer must be >= 0.3 * pipe spacing". Regarding the convective coefficient, you will have to select "internal calculation" in "Convective Heat Transfer coefficient of wall" in Type56 wall type manager. This option is available for all type of wall, except from back side of external walls. You may also have a look to the manual for more informations : "TRNSYS 16 Multizone Building Modelling with Type 56 and TRNBUILD" p 6-44. Best regards
Please, consider our environmental responsability before printing this email Le 03/04/2011 18:06, Devin Rohan a écrit : I'm using TRNSYS version 16 to model a radiant floor heating system for a single office zone/room. I have 2 questions. |