[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] Active layer for internal zones



Dear Heloise,

To define your active layer applied in an internal wall, you have to change wall category from INTERNAL to ADJACENT of the same thermal zone.

For example:
You have an INTFLOOR defined as INTERNAL in "ZoneA" without active Layer : ZoneA - INTFLOOR Internal
You put an active layer to INTFLOOR.
Then you change your INTFLOOR from INTERNAL to ADJACENT to zone "ZoneA".
With an active layer, it's possible to define an adjacent wall into the same thermal zone (that the same with chilled ceiling layer) : ZoneA - INTFLOOR (with active Layer) Adjacent to "ZoneA"

Best regards

www.itf.biz
www.itf.biz
Adrien JEZEQUEL
Simulations Thermiques Dynamiques
ITF
62, Rue du Bolliet
73230 St Alban Leysse
FRANCE
Phone :
Fax :
Mail:
+33(0) 479 750 029
+33(0) 479 852 122
a.jezequel@itf.biz
Afin de contribuer au respect de l'environnement, merci de n'imprimer cet e-mail que si nécessaire
Please, consider our environmental responsability before printing this email

Le 09/09/2010 18:21, Heloise PELEN a écrit :

Hello,

 

I would like to model a building with different thermal zones, heated by a radiative floor and ceiling. Some of my zones include more than one floor (first to third floor of my building for example).

 

I wanted to use the active layer to model this system : it works very well between two thermal zones but cannot be use in an internal layer. Hence, I cannot use it to model a radiative floor between the first and second floor of my building because there are both in the same thermal zone.

 

- I would like to understand why the active layer wasn’t designed to be use in an internal layer.

- Is there another way to model this system, using the same thermal zones ?

 

Thanks a lot for your answers.

 

Héloïse Pelen

ETAMINE

etamine_mail

heloise.pelen@etamine.coop

75 rue de la Villette - 69003 Lyon

Std : 04 37 45 34 20 / Fax : 04 37 45 41 38

Ld : 04 37 45 34 13



Visitez notre site web : www.etamine.coop !

 


---------------------------------------------------------------------------------------
Orange vous informe que cet e-mail a été contrôlé par l'anti-virus mail.
Aucun virus connu à ce jour par nos services n'a été détecté.


_______________________________________________ TRNSYS-users mailing list TRNSYS-users@cae.wisc.edu https://www-old.cae.wisc.edu/mailman/listinfo/trnsys-users