[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] Type 668 Heat Pump Performance Issues




Fred,

Heating and cooling mode in Type 668 are 100 % independent. In heating mode, only the heating performance map is called. If your data file is correct, you should see that heat is added to the load side and drawn from the source side. Make sure that the cooling control signal is left to zero.

Best regards,
Knut Erik Enerstvedt


From: trnsys-users-request@cae.wisc.edu
To: trnsys-users@cae.wisc.edu
Date: 03/09/2010 07:11 PM
Subject: TRNSYS-users Digest, Vol 63, Issue 18







Subject:
Re: [TRNSYS-users] Type 668 Heat Pump Performance Issues

Sorry, I should have been more clear. I do have the sample catalog data cooling map in there, but I am wondering if the very different capacities are effecting the results.

Are the heating and cooling mode calculations 100% independent, or are both performance maps called in the calculation?

Fred

FRED BETZ  PhD., LEED AP
SUSTAINABLE SYSTEMS ANALYST
 
AEI | AFFILIATED ENGINEERS, INC.  
5802 Research Park Blvd. | Madison, WI  53719

P: 608.236.1175 | F: 608.238.2614  
fbetz@aeieng.com  | 
www.aeieng.com  



-----Original Message-----
From: Francois Badinier [
mailto:francois.badinier@icax.co.uk]
Sent: Tuesday, March 09, 2010 11:31 AM
To: Fred Betz; trnsys-users@cae.wisc.edu
Subject: RE: [TRNSYS-users] Type 668 Heat Pump Performance Issues

Hi Fred

I don't know if it works well without a cooling map, but if you need to use
the heating mode only, you can use the default cooling file in the
"SampleCatalogData" folder to fill in the gap.

Regards,

François Badinier
Development Engineer
ICAX Ltd
1 Hatfield House
Baltic Street West
London EC1Y OST
francois.badinier@icax.co.uk
www.icax.co.uk



-----Original Message-----
From: Fred Betz [
mailto:fbetz@aeieng.com]
Sent: 09 March 2010 17:08
To: trnsys-users@cae.wisc.edu
Subject: [TRNSYS-users] Type 668 Heat Pump Performance Issues

TRNSYS Users,

I am using a type669 heat pump in heating mode only and I have entered a
performance map for the heating side.

If I am using type668 in a heating mode only way, do I need to input a
corresponding cooling map?

In other words, are both a heating and a cooling map required for proper
operation of a heat pump in heating only mode?

What I am seeing in my output is that the heat pump heats the load side, but
does not draw any heat from the source side.

Please advise,

Fred

FRED BETZ  PhD., LEED AP
SUSTAINABLE SYSTEMS ANALYST
 
AEI | AFFILIATED ENGINEERS, INC.  
5802 Research Park Blvd. | Madison, WI  53719

P: 608.236.1175 | F: 608.238.2614  
fbetz@aeieng.com  | 
www.aeieng.com  



_______________________________________________



------------------------------------------------------------------------------------------------------------
Meld deg på vårt nyhetsbrev på
www.niva.no