Dear Paul Your issue concerns Convective Heat Transfer Coefficient of wall in wall type manager. You certainly select an internal calculation for an external wall in your bui file, instead of userdefined. Message error indicates that automatic heat transfer calculation is only allowed on surface within a zone. Best regards Je serai absent du 04 Décembre 2009 au 04 Janvier 2010 I will be absent from 04th December 2009 to 04th January 2010
Please, consider our environmental responsability before printing this email PAUL COALES a écrit : Hi All I have an error reported on a simulation run and need some suggestions as to what could be going wrong. Fatal error at time 0.00 Generated by unit 3 Generated by Type56a Message Error in automatic heat transfer calcualtation for surface 7 or it's adjacent surface. Automatic heat transfer calculation is only allowed on surface within a zone. Please check input file .bui This is different to the example posted erlier in the year. I am modeling underfloor heating here. I tried deleting the surface 7 but this does not change the report. I still refers to surface 7. Any clues? I can forward the .bui file if interested. Kind Regards Paul _______________________________________________ TRNSYS-users mailing list TRNSYS-users@cae.wisc.edu https://www-old.cae.wisc.edu/mailman/listinfo/trnsys-users --------------------------------------------------------------------------------------- Orange vous informe que cet e-mail a ete controle par l'anti-virus mail. Aucun virus connu a ce jour par nos services n'a ete detecte. |