Re: [TRNSYS-users] Psychrometrics



Bastien,
 Type33 assumes that you know the dry bulb temperature. You will probably need to use some other tool (EES, perhaps) to get the temperature based on the humidity ratio and relative humidity, then use Type33 to get the enthalpy.
Kind regards,
 David


Bastien GARBAY wrote:
Dear TRNSYS users,
 
I would like to know, if there is a Psychrometrics model, which calculates the enthalpy of air in function of  two others parameters: humidity ratio and relative humidty of air.
 
Thanks for your answer.
 
Bastien Garbay