Re: [TRNSYS-users] slabcooling (minimum desired inlet massflow rate)
Dear Teodor Spita,
This minimum flow rate in an active layer is somewhat foreign and
confusing to me, but I noticed this in the text.
>From page 30 of the Volume 6 TRNBuild Manual...
"According to the equations given in the manual a specific minimum
massflow rate is necessary to assure that a linearization of the
exponential curve between inlet and outlet temperature is possible. In
most common cases the specific massflow rate has to be greater then 13
kg/hm² (the exact value is calculated for each active Layer)."
I hope this helps.
Regards,
Matt Duffy
----- Original Message -----
From: teodor.spita@hotmail.com
Sent: Wed, September 24, 2008 12:06
Subject:[TRNSYS-users] slabcooling (minimum desired inlet massflow rate)
Hellow,
Does someone know what the "minimum desired inlet mass flowrate" means in an
active layer. I don't understand the meaning of this input. I just want to
create
slabcooling with an active layer and there are 3 things to input: 1. The
inlet flow temperature, 2. the mass flow rate and 3. the minimum desired
inlet mass flowrate.
I don't understand the meaning of this third input.
thanks
Teodor Spita