[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] How to get hourly values



Henk,
 It depends which output device you are using. The printer (Type25) has a parameter that allows you to set the printing interval in hours. By default I believe that the printing interval is set to the variable name "STEP" which causes one line per time step in your output file. Be careful, however, when you set the print interval to 1, you will get the average value of each output over the preceding time step (not over the preceding hour). If you want the average value over the preceding hour, you will also have to use an integrator before the printer.
Kind regards,
 David





Technical Support Team
Thermal Energy System Specialists, LLC
2916 Marketplace Dr, Suite 104
Madison, WI 53719
techsupport@tess-inc.com

----- Original Message -----
Subject: [TRNSYS-users] How to get hourly values
From: "Henk Stijnen" <Stijnen@dwa.nl>
Date: Tue, June 10, 2008 10:21

Hi all,
 
I've a TRNsys schema with basic time step 1 hour. In consequence of convergence problems I've set in Control Cards the simulation time step to 0.125, resulting in 8 simulations per hour. And also 8 lines per hour to my output files.
Now I want to have 1 resulting line per hour. E.g. the mean value of the 8 intermediate values. How can I do that?
 
Thanks for help
 
Henk

_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@engr.wisc.edu
https://www.cae.wisc.edu/mailman/listinfo/trnsys-users