Re: [TRNSYS-users] cooling coil



Ming,
  There are three cooling coil models available in the TESS HVAC Library.

Type508 models a cooling coil using one of four control modes. The cooling coil is modeled using a bypass approach in which the user specifies a fraction of the air stream that bypasses the coil. The remainder of the air stream is assumed to exit the coil at the average temperature of the fluid in the coil and at saturated conditions. The two air streams are remixed after the coil. In its unrestrained (uncontrolled) mode of operation, the coil cools and dehumidifies the air stream as much as possible given the inlet conditions of both the air and the fluid streams. The model is alternatively able to internally bypass fluid around the coil so as to maintain the outlet air dry bulb temperature above a user specified minimum, to maintain the air outlet absolute humidity ratio above a user specified minimum or to maintain the fluid outlet temperature below some user specified maximum.

Type752 component models a simple cooling coil where the air is cooled as it passes across a coil containing a cooler fluid (typically water or a refrigerant). This model uses the bypass fraction approach for cooling coils to solve for the outlet air conditions. The bypass factor approach assumes that a portion of the air stream comes to temperature equilibrium with the coil fluid and the other portion of the air stream (the bypass fraction) is thermally unaffected by the coil in the air stream. These two flows then mix to produce the outlet air condition. This coil may operate in 1 of 4 control modes:
1 - The outlet air temperature is controlled to be at a user-specified temperature
2 - The outlet air temperature and outlet air humidity ratio are controlled to be at user-specified conditions
3 - The outlet air temperature and outlet relative humidity are controlled to be at user-specified conditions
4 - The outlet air humidity ratio is controlled to be at a user-specified condition
The big difference between Type508 and Type752 is that Type508 fully solves both the outlet air stream and outlet liquid stream conditions while Type752 solves for onlyt the air stream outlet conditions and reports the load on the liquid stream.

Type697 models a cooling coil where the air is cooled as it passes across a coil containing a cooler fluid (typically water). This model relies on user-provided external data files which contain the performance of the coil as a function of the entering air and fluid conditions. Sample data files accompany to show the format of these external files.

Kind regards,
 David


At 21:03 9/17/2006, Liu, Ming - liumy008 wrote:
Content-class: urn:content-classes:message
Content-Type: multipart/alternative;
         boundary="----_=_NextPart_001_01C6DAC6.98FD96B5"

Hello everyone,
 
I need a component ?Cooling Coil? to setup my model. One side is the secondary coolant; its inlet temperature is about -29C. The other side is air; its inlet temperature is about -22C. However, in the Cooling Coil (Type32 & Type52) in TRNSYS, air is assumed to exchange heat with water. I can not set the inlet water temperature to a minus value.
 
Is there anyone know what component I can use instead of Type 32 and Type 52?
 
Thanks in advance!
 
Ming
 
_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@engr.wisc.edu
https://www.cae.wisc.edu/mailman/listinfo/trnsys-users

****************************************************************************************
Thermal Energy System Specialists (TESS), LLC
David BRADLEY                           2916 Marketplace Drive - Suite 104
Partner                                        Madison, WI 53719
Phone: (608) 274-2577 USA
Fax: (608) 278-1475
E-mail: bradley@tess-inc.com
Web Pages:  http://www.tess-inc.com     and      http://www.trnsys.com

"Providing software solutions for today's energy engineering projects"
****************************************************************************************