Dear users,

 

I am finding that energy balance issues with type 362. I find that the energy balance does not sum zero in some conditions, I have tooled around finding that the following conditions cause the error>

·         Variable supply temperature.

·         Step signal on mass flow control signal (flow goes from 0 to full), the energy balance fails on first time steps after “ON” signal or first time steps after “OFF”.

 

I feel there is a convergence problem that does not appear on the list file. Supporting this, I tried changing the “convergence tolerance”, finding less errors on the energy balance increasing it (from default 0.0001 to 0.001).

 

I am using type362 in trnsys17 project with a simple room modelled with type 56.

 

Has anyone experienced this problem? How can it be solved?

 