berkane ahlem It is a little hard to answer without knowing the larger story of what you are trying to model. Type668 models a single speed compressor heat pump and the model computes power consumption as an output. If your system is one in which a power source charges a battery that is then used to run a heat pump then you could accomplish such a thing using Type668, controllers, and equations. If, on the other hand, your heat pump can run on a variable amount of power (for instance it may have a variable speed compressor in it so that it runs as much as it can given the input power availability) then you'd need to write a new heat pump model. kind regards, David