Is the heat pump a constant compressor speed device or does it have a variable speed compressor? If it is a constant speed device then I would recommend that you
take your experimental data and plot the heat pump power as a
function of inlet (load) temperature for some ranges of inlet
source temperature. Do the same for heat pump capacity (by using
heat pump power and COP). Those plots can then be used to generate
the performance data files that the heat pump component requires.
kind regards, David