<How can i to specify (N_Sources * n_loads) data points>
The data file takes a row of source temperatures and a row of load temperatures. If there are 7 source and 6 load temperatures then you will need to specify 42 lines of data. Please refer to the example data files for the Type 668 model and the description of Type 42 - a component that uses a similar data file structure and explains in great detail how to set up the files.
Jeff
---
Jeff Thornton President - TESS LLC 22 N. Carroll Street, Madison WI USA 53703 Office: (608) 274-2577 Fax: (608) 278-1475 www.tess-inc.com E-Mail: thornton@tess-inc.com
On 05/07/2018 10:44 pm, berkane ahlem via TRNSYS-users wrote:
Hello sir
How can i to specify (N_Sources * n_loads) data points
I used heat pump type 668in trnsys 16
Thank you
_______________________________________________ TRNSYS-users mailing list TRNSYS-users@lists.onebuilding.org http://lists.onebuilding.org/listinfo.cgi/trnsys-users-onebuilding.org