Dear Adam, You can set up a building description file .b17 in TRNBUILD with TRNFLOW information in it. In simulation studio, Type56 then has an input called TRNFLOW, which is a switch: 1 means TRNFLOW is switched on and TRNFLOW calculation will be done 0 means TRNFLOW is switched off Best _________________________________________________________________________________________________ Jakob Merk TRNSYS Software Team
Curiestraße 2 70563 Stuttgart Fax: +49 711 67976-11 Web: www.trnsys.de
Von: TRNSYS-users [mailto:trnsys-users-bounces@lists.onebuilding.org]
Im Auftrag von Adam O' Donovan via TRNSYS-users Hi All, I have a question regarding the use of TRNFLOW with Type 56. When the TRNFLOW state in TRNBUILD is switched, but is turned to 0 in the simulation studio does TRNFLOW still model infiltration and airflow? I am asking as I get different results
for a TRNFLOW on in TRNBUILD but off (i.e. 0) in the simulation studio type. As opposed to both TRNFLOW in TRNBUILD on and on (i.e. 1) in the simulation studio type. It appears to me that it calculates infiltration with TRNFLOW but without certain parameters.