[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] adding thermal capacity



Federico,

 You'd need to modify the Fortran code and make a new Type, then compile it and make a dll. The Type5 heat exchanger model is quasi steady state and you'd need to turn the solution into that of a first order differential equation in order to account for the mass of the exchanger.

kind regard,s

 David



On 10/19/2016 03:02, Federico Bava via TRNSYS-users wrote:

Hello everyone,

 

I would like to add some thermal capacity to a heat exchanger (type5) to take into account the metal mass of a flat plate heat exchanger. Is there any one with some suggestions/ideas on how this can be done with some workaround?

 

Thanks in advance and best regards,

 

Federico

 



_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@lists.onebuilding.org
http://lists.onebuilding.org/listinfo.cgi/trnsys-users-onebuilding.org

-- 
***************************
David BRADLEY
Principal
Thermal Energy Systems Specialists, LLC
22 North Carroll Street - suite 370
Madison, WI  53703 USA

P:+1.608.274.2577
F:+1.608.278.1475
d.bradley@tess-inc.com

http://www.tess-inc.com