Dear Martin,

You should write the complete path to your building file in type 56, even if it is located in the same directory as the project. 
Which optimization method are you using?
If you are trying to use PSO or similar optimization method, which runs parallel trnsys simulations, you should limit the no. of cores used to 1. For some reason, Trnbuild locks the building file, so multiple instances of the simulation are not possible. However, you can try to run trn.exe in batch from genopt directly (without trnopt)  to avoid this.

Hope this helps.

Regards,

Marko
 

From: "trnsys-users-request@lists.onebuilding.org" <trnsys-users-request@lists.onebuilding.org>
To: trnsys-users@lists.onebuilding.org
Sent: Wednesday, April 15, 2015 10:05 PM
Subject: TRNSYS-users Digest, Vol 124, Issue 20

----- Forwarded Message -----

Send TRNSYS-users mailing list submissions to
    trnsys-users@lists.onebuilding.org

To subscribe or unsubscribe via the World Wide Web, visit
    http://lists.onebuilding.org/listinfo.cgi/trnsys-users-onebuilding.org

or, via email, send a message with subject or body 'help' to
    trnsys-users-request@lists.onebuilding.org

You can reach the person managing the list at
    trnsys-users-owner@lists.onebuilding.org

When replying, please edit your Subject line so it is more specific
than "Re: Contents of TRNSYS-users digest..."

Today's Topics:

  1. Genopt trnbuild error (Martin Berov)
  2. Re: Genopt trnbuild error (mcdowell@tess-inc.com)
Hi,

I'm using Genopt to optimize parameters of solar heating system (first just the collector area and slope). I compiled the input file, defined the variables in genopt i.e. everything as required. bu when I run the optimization i get error message as table where is written:

Trnbuild
Surf-No                                       Description                                       Comment
-1                                          no OUTPUT's specified                     please add at least one output

In the Trnsys simulation environment I get output results (the model is properly functioning)

Do you have idea what could be the problem?

Best Regards
Martin

Martin Berov -
It is not finding your building model file when it starts the simulation.  GenOpt moves the files to run a simulation so you need to make sure all paths for files are complete.
Regards,
Tim
 
---
Timothy P. McDowell Executive Vice President Thermal Energy System Specialists, LLC 22 N Carroll St, Suite 370 Madison, WI 53703 608-274-2577
On 2015-04-14 14:06, Martin Berov wrote:
Hi,
 
I'm using Genopt to optimize parameters of solar heating system (first just the collector area and slope). I compiled the input file, defined the variables in genopt i.e. everything as required. bu when I run the optimization i get error message as table where is written:
 
Trnbuild
Surf-No                                       Description                                       Comment
-1                                          no OUTPUT's specified                     please add at least one output
 
In the Trnsys simulation environment I get output results (the model is properly functioning)
 
Do you have idea what could be the problem?
 
Best Regards
Martin
 

_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@lists.onebuilding.org
http://lists.onebuilding.org/listinfo.cgi/trnsys-users-onebuilding.org

_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@lists.onebuilding.org
http://lists.onebuilding.org/listinfo.cgi/trnsys-users-onebuilding.org