Sergio, The first line of the data file contains values of normalized pump speed (rotational speed over rotational speed at full-speed operation). The second line contains values of pump flow rate (in L/s). The rest of the lines contain two values each. The first is the pump head [m] and the second is the pump efficiency [0..1] for each combination of normalized pump speed and pump flowrate listed in the first two lines. The data file should be constructed from manufacturer's data on the pump that you are planning to use in your simulation. Kind regards, David On 12/17/2014 14:31, sergio morales
wrote:
-- *************************** David BRADLEY Principal Thermal Energy Systems Specialists, LLC 22 North Carroll Street - suite 370 Madison, WI 53703 USA P:+1.608.274.2577 F:+1.608.278.1475 d.bradley@tess-inc.com http://www.tess-inc.com http://www.trnsys.com |