Use an Equation and multiply together the control signal for the pump (and others if necessary) and the output from an annual forcing function.  Then drive the pumps/heaters with the new control signal. The forcing function would be set to 1 for the balance of the year and to 0 for the summer:

 

Unit 1 Type 14 Forcing Function: Summer

Parameters 12

0,0  3624,0  3624,1  5088,1  5088,0  8760,0

 

Unit 2 Type X Solar Controller

<Snip>

 

Equations 3

Summer=[1,1]

OK_Solar=[2,1]

_On_SolarPump_=(1-Summer)*OK_Solar

 

Jeff

 

---
Jeff Thornton President - TESS LLC 22 N. Carroll Street, Madison WI USA 53703 Office: (608) 274-2577 Fax: (608) 278-1475 www.tess-inc.com E-Mail: thornton@tess-inc.com

On 05/06/2014 1:59 pm, Aamir Mehmood wrote:

Respected Sir,
Kindly guide me how solar collector operation can be stopped for a specific time period?
Actually I want to stop the operation of solar water heater system for summer months. Which function can be used for this purpose and in what way?
Waiting for your kind reply!

Best Regards,
Aamir Mehmood
Post-Graduate Researcher
Center for Energy Systems (CES)
National University of Sciences and Technology (NUST),
Islamabad, Pakistan.
Mob: +92-300-650-7809