You enter the total array area and the total array flow rate.  The model will set the flows to each collector internally based on the number in series parameter.  This parameter does have an impact on the results when you correctly set the flow.  Typically a system with 6 collectors in parallel will have a flow rate 6x the flow of a system with 6 collectors in series.  

Jeff

Sent from my iPhone

On May 3, 2014, at 5:24 AM, saja al-rifai <srhihi2003@yahoo.com> wrote:

Dear all

I am doing on design the solar thermal cooling system by using TRNSYS, I simulate the system by used flat plate collectors or evacuated tube, there is an problem in (number in series ) parameter i entered different values but the simulation results doesn't change, also i don't know how the TRNSYS  deals with the flow rate and area. Is this the value of flow that pass in each cell or is the final outlet flow rate (flow to storage tank) after divided the collector to parallel and series???