Benoît, I don't know whether you are trying to run an automatic optimization or not but the only solution I can think of is to make a series of buildings (*.b17 files) each with a variation of the wall in it. Put in an ASSIGN statement for each one of the *.b17 files and give each its own unique logical unit number. Then define a CONSTANT for the logical unit of the *.b17 file that Type56 will use. Then you can run a parametric study where you change the logical unit with each run. Regards, David On 10/25/2013 08:03, benoit schmitt wrote: