Re: [TRNSYS-users] naturel ventilation



There is also a new Type 98 that has been developed that provides a more complete coupling between CONTAM and TRNSYS Type 56. A set of tools has also been developed to assist in implementing this coupling. You can find out more about it on the NIST website.

http://www.bfrl.nist.gov/IAQanalysis/CONTAM/overview/2.htm

http://www.bfrl.nist.gov/IAQanalysis/CONTAM/manual/CWHelp31.htm -> Using CONTAM -> Working with TRNSYS.

 

- Stuart

 

 

From: Karol Bandurski [mailto:karol.bandurski@put.poznan.pl]
Sent: Tuesday, March 26, 2013 9:59 AM
To: 'TRNSYS users mailing list at the Solar Energy Lab, UW-Madison'
Subject: Re: [TRNSYS-users] naturel ventilation

 

Hi,

 

Honestly  firstly it should be stated that natural ventilation is so complex phenomena that simulation of this issue is very difficult – there is a lot of uncertainty (e.g. wind Cp value)

 

Using Type 56 (TRNBuild) you can only define natural ventilation (infiltration, ventilation mode, coupling flow of walls).

 

To simulate natural ventilation accurately you should try to use CFD software (Fluent/ANSYS, OpenFOAM-HVACTool, OpenFOAM-Helyx), there is possibility to coupling this softs with TRNSYS e.g. type 101.

 

You can try to simulate it in more coarse way using airflow network method/software – e.g. Contam, ESP-r or commercial TRNBuild plug-in: TRNFLOW.

There is possibility to coupling Contam or ESP-r model with TRNBuild – see type 97 and 130.

 

Contam is free airflow and contaminant distribution simulation software, ESP-r is free building performance (both thermal and airflow) simulation software.

 

Good luck,

Karol

 

 

 

 

 

From: jihad alaoui sosse [mailto:sys.energie@gmail.com]
Sent: Monday, March 25, 2013 4:09 PM
To: TRNSYS-users@cae.wisc.edu
Subject: [TRNSYS-users] naturel vantilation

 

how to model a naturel ventilation in a multizone building 

Cordialy.

--

                                              

Jihad Alaoui Sosse

Ingénieur d'étude

Département Energie

Tél : O648883325 ;

Courriel : sys.energie@gmail.com

NOVEC,  Filiale de CDG Développement - Groupe CDG

Angle Avenue Annakhil et Mehdi Ben Barka

Espace les Palmiers – Hay Riad – Rabat - MAROC

Site web : www.novec.ma

 

P Avant d'imprimer, pensez à l'environnement !