Leen,
  The 6th output of Type91 is the heat exchanger UA (in kJ/h.K). It is mislabeled in the Studio proforma. Thanks for pointing that out.
Best,
 David


On 11/11/2012 07:27, leen peeters wrote:
Dear all,
 
I put 0.89 as input for the effectiveness of the heat exchanger and when I plot the output effectivenss I get values as high as 746. Anyone experienced that before?
Calculting the effectiveness based on the TRNEXE temperatures gives what I expect, not something that conflicts with the first law of thermodynamics ;-)
 
 
leen