Karol, In general the notice has
nothing to do with a frozen TRNEXE.exe, it is just an information. The message indicates
that the internal controller for turning on the integrated heating/cooling
has convergence problems and a deadband is applied to promote convergence. This may be the case at
the moment of turning ON or OFF something. After 6 internal iterations
a deadband is added to promote convergence. If the convergence isn’t
reached after 12 iterations a warning is written to the lst/log file. Regards, Dipl.-Ing.
Geschäftsführer:
Dipl.Ing. Matthias Schuler, Dipl.Ing. Von: Karol Bandurski
[mailto:karol.bandurski@put.poznan.pl] Dear All, I try to simulate dwelling with natural ventilation. I set some
algorithm for window opening and ideal heating for colder part of year for each
zone with set temperature depending on time of day. When I run my yearly simulation it stop in one moment and TRNEXE is
frozen... There is even no error! Then I can only turn off TRNEXE. Only think what appear (many times) in .lst file is Notice: More than 6 iterations for internal regulation HEATING/COOLING. I will be grateful for any advice! I enclose .lst file. Regards, ------------------------------------------------ Karol Bandurski MSc. Institute
of Environmental Engineering |