[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] heat capacitance of furnishings ect.



Karol,
The general rule of thumb that I use is 5 times the default (which accounts only for the thermal capacitance of the air). The formula ends up being ZoneVolume*1.2*1.007*5 (1.2 is the density of air, 1.007 is the specific heat)
Best,
 David


On 7/17/2012 06:01, Karol Bandurski wrote:

Dear All,

 

I model block of flats in TRNSYS. One Dwelling is one zone.

I am wondering how can I estimate heat capacitance of zones. I take into account partition walls and air, but what about furniture and other equipment?

 

Do you have some idea/experience? maybe some constant coefficient should be applied by me?

 

Regards,

Karol

------------------------------------------------

Karol Bandurski MSc.

Institute of Environmental Engineering

Poznan University of Technology

www.ee.put.poznan.pl

www.put.poznan.pl

 

 



_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu
https://mailman.cae.wisc.edu/listinfo/trnsys-users

-- 
***************************
David BRADLEY
Principal
Thermal Energy Systems Specialists, LLC
22 North Carroll Street - suite 370
Madison, WI  53703 USA

P:+1.608.274.2577
F:+1.608.278.1475
d.bradley@tess-inc.com

http://www.tess-inc.com