David,
Thanks for the answer. But the problem is that it isn't a 100% false ceiling but about 70%. So what do I do with the "air - air contact" between the two zones. Does Trnsys takes this into account when I model it with a virtual surface in google sketchup or do the airnodes then have to belong to the same thermal zone?
Greetings, Joke
Van: David BRADLEY [d.bradley@tess-inc.com]
Verzonden: maandag 17 oktober 2011 18:38 Aan: Joke De Beuckelaer CC: TRNSYS-users Onderwerp: Re: [TRNSYS-users] Simulation of false ceiling: influence on inertia Joke,
I like to simulate this situation as two thermal zones; the conditioned zone below and the plenum zone above. Because the suspended ceiling basically has no mass to it, I simulate it as a wall made up of a single purely resistive (ie massless) layer. best, David On 10/14/2011 03:44, Joke De Beuckelaer wrote: