[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] TRNSYS-users Digest, Vol 77, Issue 24



Thank you, thank you very much.
I'm preparing my memoiry of master i'm special in mechanic engeneering of thermal power, my memoiry is about ISCC integrated solai combine cycle systeme, if you have in exemple projet in transys about this send it please to study it

2011/5/8 <trnsys-users-request@cae.wisc.edu>
Send TRNSYS-users mailing list submissions to
       trnsys-users@cae.wisc.edu

To subscribe or unsubscribe via the World Wide Web, visit
       https://mailman.cae.wisc.edu/listinfo/trnsys-users
or, via email, send a message with subject or body 'help' to
       trnsys-users-request@cae.wisc.edu

You can reach the person managing the list at
       trnsys-users-owner@cae.wisc.edu

When replying, please edit your Subject line so it is more specific
than "Re: Contents of TRNSYS-users digest..."

Today's Topics:

  1. Re: TRNSYS-users Digest, Vol 76, Issue 38 (WALID KADRI)
  2. Re: TRNSYS-users Digest, Vol 76, Issue 36 (WALID KADRI)


---------- Message transféré ----------
From: WALID KADRI <walidenergetique@gmail.com>
To: trnsys-users@cae.wisc.edu
Date: Sat, 7 May 2011 23:58:39 +0200
Subject: Re: [TRNSYS-users] TRNSYS-users Digest, Vol 76, Issue 38
Thank you, thank you very much.
I'm preparing my memoiry of master i'm special in mechanic engeneering of thermal power, my memoiry is about ISCC integrated solai combine cycle systeme, if you have in exemple projet in transys about this send it please to study it.

2011/4/11 <trnsys-users-request@cae.wisc.edu>
Send TRNSYS-users mailing list submissions to
       trnsys-users@cae.wisc.edu

To subscribe or unsubscribe via the World Wide Web, visit
       https://mailman.cae.wisc.edu/listinfo/trnsys-users
or, via email, send a message with subject or body 'help' to
       trnsys-users-request@cae.wisc.edu

You can reach the person managing the list at
       trnsys-users-owner@cae.wisc.edu

When replying, please edit your Subject line so it is more specific
than "Re: Contents of TRNSYS-users digest..."

Today's Topics:

  1. Re: time delay by means of type 93 (input value recall)
     (Matt Duffy)


---------- Message transféré ----------
From: "Matt Duffy" <duffy@tess-inc.com>
To: "Stefan Wachter" <wachter@mail.hs-ulm.de>, trnsys-users@cae.wisc.edu
Date: Mon, 11 Apr 2011 15:35:35 -0500 (CDT)
Subject: Re: [TRNSYS-users] time delay by means of type 93 (input value recall)

Hello Stefan,

As long as you implement the timestep as a fraction in an EQUATIONS in the control cards, you should be ok. For example,

EQUATIONS 1
TIMESTEP=2/60 !Timestep of 2 mins

Please see the attached for reference.


Best regards,

Matt Duffy


----- Original Message -----
From: "Stefan Wachter" <wachter@mail.hs-ulm.de>
Sent: Fri, April 8, 2011 4:05
Subject: [TRNSYS-users] time delay by means of type 93 (input value recall)

Hello everybody,
 
I am new at trnsys-users.
Currently I`m modeling an already existing solar heating system (for hot water).
In this system the loading pump is activated by a time delay of 4 minutes (after solar pump is launched).
I tried to model this as follows:
 
- simulation time step: 2 minutes
- storage of the control signal of the solar pump over the last two time steps by means of type 93 (input value recall)
- if the control signal of the solar pump is "1" in the stored two time steps, then the loading pump is launched.
 
It works (tried by a simple example deck) but does it also works in context with a quite big deck (120 m² apertur area, 2 continuous controllers)?
I`m concerned about that the small time step of 2 minutes could cause problems (for example oscillations of the controllers).
Could this work or have someone of you another idea how i can solve this problem?
 
Thanks a lot.
Best regards.
 
Stefan Wachter 
 
 
 

_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu
https://mailman.cae.wisc.edu/listinfo/trnsys-users

_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu
https://mailman.cae.wisc.edu/listinfo/trnsys-users




---------- Message transféré ----------
From: WALID KADRI <walidenergetique@gmail.com>
To: trnsys-users@cae.wisc.edu
Date: Sun, 8 May 2011 00:01:11 +0200
Subject: Re: [TRNSYS-users] TRNSYS-users Digest, Vol 76, Issue 36
Thank you, thank you very much.
I'm preparing my memoiry of master i'm special in mechanic engeneering of thermal power, my memoiry is about ISCC integrated solai combine cycle systeme, if you have in exemple projet in transys about this send it please to study it

2011/4/11 <trnsys-users-request@cae.wisc.edu>
Send TRNSYS-users mailing list submissions to
       trnsys-users@cae.wisc.edu

To subscribe or unsubscribe via the World Wide Web, visit
       https://mailman.cae.wisc.edu/listinfo/trnsys-users
or, via email, send a message with subject or body 'help' to
       trnsys-users-request@cae.wisc.edu

You can reach the person managing the list at
       trnsys-users-owner@cae.wisc.edu

When replying, please edit your Subject line so it is more specific
than "Re: Contents of TRNSYS-users digest..."

Today's Topics:

  1. NTYPE 906: Energy balance for surfaces (??)


---------- Message transféré ----------
From: 王洋 <wanghongyang1767@gmail.com>
To: trnsys-users@cae.wisc.edu
Date: Mon, 11 Apr 2011 17:07:35 +0200
Subject: [TRNSYS-users] NTYPE 906: Energy balance for surfaces
Dear all,

    I have some questions about NTYPE 906: Energy balance for surfaces:

   1. Please see the ATTACHED.
     
      Based on the Manual, B6_BAL should be always 0, but here i think its calculation is wrong. B6_BAL isn't -8.180E-13, it should be 2.683E-03, so it's not 0, PLEASE tell me some possible reasons about it.
     1_B6_BAL  = -   1_B6_DQWALLdt-   1_B6_QCOMI+   1_B6_QCOMO+   1_B6_QRADGI+    1_B6_QRADGO-    1_B6_QALG

      -8.180E-13     -3.838E+03      2.683E-03     -3.838E+03      0.000E+00      0.000E+00      0.000E+00
2. B6_DQWALLdt in Manual is change of internal energy of surface, but it's a little abstract. Here I only used the heatings in TRNBUILD, no other internal gains. PLEASE give me some examples about change of internal energy of surface. Is it energy Generation of Wall etc.? Why here is minus (-3.838E+03)? What's difference between  B6_DQWALLdt and B6_QCOMO? Why here they are the same? Is there some reasons?

3. I think B6_QCOMI is some heat flux enter into inside of wall such as the heat from the heatings of indoor and the solar radiation, Is it right?   B6_QCOMO is heat loss from the wall outside, Is it right? If wrong, PLEASE tell me what are their meaning.

Thanks!

br.

wang


---------- Forwarded message ----------
From: 王洋 <wanghongyang1767@gmail.com>
Date: 2011/3/8
Subject: NTYPE 906: Energy balance for surfaces
To: trnsys-users@cae.wisc.edu


Dear all,

    I have some questions about NTYPE 906: Energy balance for surfaces:

   1. Please see the ATTACHED.
     
      Based on the Manual, B6_BAL should be always 0, but here i think its calculation is wrong. B6_BAL isn't -8.180E-13, it should be 2.683E-03, so it's not 0, PLEASE tell me some possible reasons about it.
     1_B6_BAL  = -   1_B6_DQWALLdt-   1_B6_QCOMI+   1_B6_QCOMO+   1_B6_QRADGI+    1_B6_QRADGO-    1_B6_QALG

      -8.180E-13     -3.838E+03      2.683E-03     -3.838E+03      0.000E+00      0.000E+00      0.000E+00
2. B6_DQWALLdt in Manual is change of internal energy of surface, but it's a little abstract. Here I only used the heatings in TRNBUILD, no other internal gains. PLEASE give me some examples about change of internal energy of surface. Is it energy Generation of Wall etc.? Why here is minus (-3.838E+03)? What's difference between  B6_DQWALLdt and B6_QCOMO? Why here they are the same? Is there some reasons?

3. I think B6_QCOMI is some heat flux enter into inside of wall such as the heat from the heatings of indoor and the solar radiation, Is it right?   B6_QCOMO is heat loss from the wall outside, Is it right? If wrong, PLEASE tell me what are their meaning.

Thanks!

br.

wang




2011/3/7 王洋 <wanghongyang1767@gmail.com>



2011/3/7 <trnsys-users-request@cae.wisc.edu>
Send TRNSYS-users mailing list submissions to
       trnsys-users@cae.wisc.edu

To subscribe or unsubscribe via the World Wide Web, visit
       https://mailman.cae.wisc.edu/listinfo/trnsys-users
or, via email, send a message with subject or body 'help' to
       trnsys-users-request@cae.wisc.edu

You can reach the person managing the list at
       trnsys-users-owner@cae.wisc.edu

When replying, please edit your Subject line so it is more specific
than "Re: Contents of TRNSYS-users digest..."

Today's Topics:

  1. Re: Strange error (hotline)
  2. Questions...please reply (Juv?ncio Correia Tavares)


---------- 已转发邮件 ----------
From: "hotline" <hotline@transsolar.com>
To: rraye001 <rraye001@fiu.edu>
Date: Mon, 7 Mar 2011 13:33:34 +0100
Subject: Re: [TRNSYS-users] Strange error
Hi,
 
seems like you hit a limit for the generation of the transfer function coefficients.
Please check if the roof is defined correctly.
 
Regards
Christian
 

TRANSSOLAR Software Team

hotline@transsolar.com

 

www.trnsys.de

Transsolar KlimaEngineering - Technologien für energieeffizientes Bauen und Nutzerkomfort in Gebäuden                                   

Transsolar Energietechnik GmbH, Curiestrasse 2, 70563 Stuttgart / Amtsgericht Stuttgart - HRB 23347 / UsSt.-Id: DE152272639

Geschäftsführer: Dipl.Ing. Matthias Schuler, Dipl.Ing. Thomas Auer, Dipl.Phys. Stefan Holst, Prof. Volkmar Bleicher

 


   Von: Rambod Rayegan [mailto:rraye001@fiu.edu]
Gesendet: Samstag, 5. März 2011 06:08
An: trnsys-users@cae.wisc.edu
Betreff: [TRNSYS-users] Strange error

Dear TRNSYS users:

 
I am working on a model created buy TRNSYS 3d plugin in google sketchup for couple of months. Everyday I add  something to it or modify some parameters in it. Today, I have just changed the roof type in the building type 56 and tried to run it again but I have received the following error:
 
 
Visual Fortran run-time error
 
fortrtl:severe(64):input conversion error, unit 56, file C:\.....building.trn 
Image PC Routine Source DFORRT.DLL  02014C49 Unknown  Unknown Unknown
 
 
Anybody has an idea to solve the issue?
 
Thank you.

Rambod Rayegan
Ph.D Candidate
Mechanical Engineering Department
Florida International University
10555 W Flagler St, EC3620
Miami, FL, 33174
 
305-348-3558 (Office)
786-218-7375(Cell)
305-348-1932 (Fax)



---------- 已转发邮件 ----------
From: "Juvêncio Correia Tavares" <juvenciotavares@hotmail.com>
To: <trnsys-users@engr.wisc.edu>
Date: Fri, 4 Mar 2011 15:16:10 +0000
Subject: [TRNSYS-users] Questions...please reply

I`m
 doing a dynamic simulation of buildings in TRNSYS, during the simulation gave the following error ... as you can see in the picture.

And also, I would like to send me a PDF about connection.

I await your response.

thanks.

_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu
https://mailman.cae.wisc.edu/listinfo/trnsys-users





_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu
https://mailman.cae.wisc.edu/listinfo/trnsys-users



_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu
https://mailman.cae.wisc.edu/listinfo/trnsys-users