[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] Error and Fan coil, radiator model



Muhammad,
  The excel file has most of the data that you need in it in rows 9-17. The independent variables required by Type938's data file (the lines across the top of the file) are the temperatures in column B and the dependent variable values are in column C or D. The map given in the data file is not complete (ie not all combinations are given). What I would recommend you do is to normalize the data in your excel spreadsheet (divide all of the power values by the power at rated conditions) then overlay that normalized data on a plot of the example Type938 data.  You should find that your data, once normalized, fits pretty well with the example normalized data, in which case you can use the default data file.
Kind regards,
 David


On 3/4/2011 04:50, muhammad waseem wrote:
Hi David,
Thanks for your kind reply. I fixed my errors. Now the problem is I can not understand how to make external file for my heat pump. I am using type 938. The data which I get from manufacture is in attached file, Which is not as it was written as default in type 938. I am attaching manufacture data and Type 938 data file.
 
I hope to hearing from you soon.
 
Kindest Regards

On Wed, Mar 2, 2011 at 4:15 PM, David BRADLEY <d.bradley@tess-inc.com> wrote:
Muhammad,
  In order to run your simulation, I would need the data files for the Type534 tank and for the Type938 heat pump. The *.lst and *.log files contain information as to the cause of the error. As for a radiator and a fancoil model, both are available in the TESS HVAC Library for Trnsys17.
Kind regards,
 David



On 3/1/2011 04:29, muhammad waseem wrote:
Hi,
I have simulated a Solar assisted heat pump system. I am getting some errors, could not understand what these for? Could any one please help me out.
Also does any one know any models for radiator and fan coil unit. If there is no standard model then how I can get non standard models? Attached with this email is my project's .tpf file.
 
 
Thanks
 
Looking forward to hearing from you.

 
 
Kindest Regards

--
MUHAMMAD WASEEM AHMAD
Loughborough University.
_______________________________________________ TRNSYS-users mailing list TRNSYS-users@cae.wisc.edu https://mailman.cae.wisc.edu/listinfo/trnsys-users

-- 
***************************
David BRADLEY
Principal
Thermal Energy Systems Specialists, LLC
22 North Carroll Street - suite 370
Madison, WI  53703 USA

P:+1.608.274.2577
F:+1.608.278.1475
d.bradley@tess-inc.com

http://www.tess-inc.com
http://www.trnsys.com



--
MUHAMMAD WASEEM AHMAD
PHD RESEARCHER
BUILDING ENERGY RESEARCH GROUP,
DEPARTMENT OF CIVIL AND BUILDING ENGINEERING,
LOUGHBOROUGH UNIVERSITY,
LOUGHBOROUGH, UK

-- 
***************************
David BRADLEY
Principal
Thermal Energy Systems Specialists, LLC
22 North Carroll Street - suite 370
Madison, WI  53703 USA

P:+1.608.274.2577
F:+1.608.278.1475
d.bradley@tess-inc.com

http://www.tess-inc.com
http://www.trnsys.com