Wang,
 you have the thickness of your brick layer set to zero:

WALL WALL001
 LAYERS   = BRICK
 THICKNESS= 0    
 ABS-FRONT= 0.6   : ABS-BACK= 0.6 
 EPS-FRONT= 0.9   : EPS-BACK= 0.9 
 HFRONT   = 11 : HBACK= 64

open the wall type manager and set a thickness for the brick. It is still does not find the transfer function coefficients you may need to decrease the timebase. Increasing the time base helps if you have high mass, thick walls. Decreasing helps if you have lightweight low mass walls.
David


On 2/17/2011 11:21, 王洋 wrote:
Dear all,

I met this error:


          ***** WALL TRANSFERFUNCTION CALCULATIONS *****

 UNABLE TO FIND A ROOT AFTER INDICATION THAT A ROOT EXISTED
 
 CHECK THE WALL TYPE AFTER THE LAST CALCULATED WALL
 OFTEN THE WALL CAPACITY IS TO SMALL TO CALCULATE A TRANSFER FUNCTION !
 
 CHECK ALSO YOUR TIMEBASE !



Attached is INF file, Please check it!


And I make the timebase larger, but it still doesn't work.

Many thanks!

Br.

wang



2011/2/16 <trnsys-users-request@cae.wisc.edu>
Send TRNSYS-users mailing list submissions to
       trnsys-users@cae.wisc.edu

To subscribe or unsubscribe via the World Wide Web, visit
       https://mailman.cae.wisc.edu/listinfo/trnsys-users
or, via email, send a message with subject or body 'help' to
       trnsys-users-request@cae.wisc.edu

You can reach the person managing the list at
       trnsys-users-owner@cae.wisc.edu

When replying, please edit your Subject line so it is more specific
than "Re: Contents of TRNSYS-users digest..."

Today's Topics:

  1. length and witdh from the collector area (Sancho,Fernando)
  2. Re: g95 compiler (Francois Badinier)


---------- 已转发邮件 ----------
From: "Sancho,Fernando" <fsancho@sonnenwaermeag.de>
To: <trnsys-users@cae.wisc.edu>
Date: Wed, 16 Feb 2011 11:48:55 +0100
Subject: [TRNSYS-users] length and witdh from the collector area

Hello TRNSYS-users,

 

I’m making simulations with plastic collector. Many from the commercial models can be resized, so it’s almost free how to configurate the collector area. I would like to find  an optimal distribution, dependent of course on Radiation, temperatures etc…, basically how long and width for a minimum output temperature of  the fluid. Or just what is the best for a certain situation 10m*30m or 30m*10m ?.

I ´ve already done my calculations with Excel and know that longer means higher output temperature but lower energy gain… but with trnsys  it’s difficult to face the problem ,

do I take a standard unit and probe around different series und parallel distributions L ?

Do type 553 and 559 in TESS TRn17 do that; difference width and length (I didn’t find it in the general pdf… and have just occasionally access to TRNSYS17)?

Any advice or experience?

 

So Thanks a lot!!!!!

 

 

 

 

Mit freundlichen Grüßen

Fernando Sancho Márquez

PHÖNIX SonnenWärme AG

____________________________________________
PHÖNIX Sonnenwärme AG
Ostendstr. 1

D-12459 Berlin

 



---------- 已转发邮件 ----------
From: "Francois Badinier" <francois.badinier@icax.co.uk>
To: <mabadie@univ-lr.fr>, <trnsys-users@cae.wisc.edu>
Date: Wed, 16 Feb 2011 15:02:13 -0000
Subject: Re: [TRNSYS-users] g95 compiler
Marc

If you still want to use g95, an alternative is to define T0, Tfinal and
Timestep as parameters in our new component. The only drawback is that you
have to be careful to change those values whenever you change them in the
simulation studio.

Regards,

François Badinier
Development Engineer
ICAX Ltd
1 Berry Street
London EC1M 5PS
francois.badinier@icax.co.uk
www.icax.co.uk



-----Original Message-----
From: trnsys-users-bounces@cae.wisc.edu
[mailto:trnsys-users-bounces@cae.wisc.edu] On Behalf Of mabadie@univ-lr.fr
Sent: 14 February 2011 11:57
To: trnsys-users@cae.wisc.edu
Subject: Re: [TRNSYS-users] g95 compiler

Danny and David,

I actually successfully used the G95 compiler with TRNSYS 16 to create
new components. However, i was not able to properly used TRNSYS
variables (such as getSimulationTime()) in my TYPES. The only solution
i found was to stop using this compiler and buying Intel Fortran v11.

I hope you will find a way to fix that problem as it is nice to have
the choice of a free/light fortran compiler.

Best,

-- Marc O. Abadie


David BRADLEY <d.bradley@tess-inc.com> a écrit :

> Danny,
>   getSimulationTime is a function that is defined in the data module
> called "TrnsysFunctions." When compiling an external Type in either
> the Compaq or the Intel compilers, I have to make sure that the
> compiler is set to look for data modules (sometimes called MOD
> files) in the ..\Trnsys17\Compilers\IVF111\Debug\ directory or else
> copy them to some other place where they can be found by the
> compiler. My understanding is that this tells the compiler "don't
> worry, even though I haven't defined this function called
> getSimulationTime() in my external Type242.dll, you'll find that
> function during run-time because my dll will be called by a dll in
> which the function is defined"
>
>   I don't know how the G95 compiler handles settings for where to
> look for *.mod files but this is not specific to Trnsys17, there
> were a number of TrnsysFunctions called by Types in Trnsys16 as
> well. We have just expanded their use in Trnsys17.
> best,
>  David
>
>
> On 2/11/2011 11:12, Danny Jonas wrote:
>>
>> Dear TRNSYS users,
>>
>> I have use the directions in the document, but after starting the
>> batch file to compile my own type I've received the following
>> message:
>>
>> "In file Type201.for:72
>>
>>                Time=getSimulationTime<>
>>
>> Error: Function 'getsimulationtime' at <1> has no implicit type"
>>
>> could the error be associated with using TRNSYS17?
>>
>> Using the example (type242), I can build the type242.dll.
>>
>> I'm now trying to use C++, till now it works fine. But I still
>> don't understand why it doesn't work with the batch file as fortran
>> code....
>>
>> Thanks a lot,
>>
>> Best Regards,
>>
>> Danny
>>
>> -----Ursprüngliche Nachricht-----
>>
>> Von: Daniel Bergey [mailto:daniel@buildingscience.com]
>>
>> Gesendet: Mittwoch, 9. Februar 2011 21:14
>>
>> An: Danny Jonas
>>
>> Betreff: Re: [TRNSYS-users] g95 compiler
>>
>> I have successfully compiled a couple of components using
>> directions in the attached document.  I don't recall the URL whence
>> I downloaded it originally.  Sorry about the doc format; let me
>> know if I should convert it.
>>
>> Daniel
>>
>> On Fri, Feb 04, 2011 at 01:33:49PM +0100, Danny Jonas wrote:
>>
>>>    Dear TRNSYS users,
>>
>>>
>>
>>>
>>
>>>
>>
>>>    I want to use the free g95 compiler to create my own components
>>> in TRNSYS.
>>
>>>
>>
>>>
>>
>>>
>>
>>>    I have found the following message in the TRNSYS-users Archives:
>>
>>>
>>
>>>
>>
>>>
>>
>>>
>>
>>> [1]http://mailman.cae.wisc.edu/pipermail/trnsys-users/2008/003957.html
>>
>>>
>>
>>>
>>
>>>
>>
>>>    with the following link:
>>
>>>
>>
>>>
>>
>>>
>>
>>>    [2]http://software.cstb.fr/main/articles.asp?langue=us
>>
>>>
>>
>>>
>>
>>>
>>
>>>    But this page no longer exists.
>>
>>>
>>
>>>
>>
>>>
>>
>>>    Can someone send a link where I can download this example?
>>
>>>
>>
>>>
>>
>>>
>>
>>>
>>
>>>
>>
>>>    Thanks in advance,
>>
>>>
>>
>>>
>>
>>>
>>
>>>
>>
>>>
>>
>>>    Danny
>>
>>>
>>
>>>
>>
>>>
>>
>>> References
>>
>>>
>>
>>>    Visible links
>>
>>>    1.
http://mailman.cae.wisc.edu/pipermail/trnsys-users/2008/003957.html
>>
>>>    2. http://software.cstb.fr/main/articles.asp?langue=us
>>
>>> _______________________________________________
>>
>>> TRNSYS-users mailing list
>>
>>> TRNSYS-users@cae.wisc.edu <mailto:TRNSYS-users@cae.wisc.edu>
>>
>>> https://mailman.cae.wisc.edu/listinfo/trnsys-users
>>
>>
>> _______________________________________________
>> TRNSYS-users mailing list
>> TRNSYS-users@cae.wisc.edu
>> https://mailman.cae.wisc.edu/listinfo/trnsys-users
>
> --
> ***************************
> David BRADLEY
> Principal
> Thermal Energy Systems Specialists, LLC
> 22 North Carroll Street - suite 370
> Madison, WI  53703 USA
>
> P:+1.608.274.2577
> F:+1.608.278.1475
> d.bradley@tess-inc.com
>
> http://www.tess-inc.com
> http://www.trnsys.com
>
>


_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu
https://mailman.cae.wisc.edu/listinfo/trnsys-users



_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu
https://mailman.cae.wisc.edu/listinfo/trnsys-users


_______________________________________________ TRNSYS-users mailing list TRNSYS-users@cae.wisc.edu https://mailman.cae.wisc.edu/listinfo/trnsys-users

-- 
***************************
David BRADLEY
Principal
Thermal Energy Systems Specialists, LLC
22 North Carroll Street - suite 370
Madison, WI  53703 USA

P:+1.608.274.2577
F:+1.608.278.1475
d.bradley@tess-inc.com

http://www.tess-inc.com
http://www.trnsys.com