Re: [TRNSYS-users] Zone capacitance
The default capacitance (1.2*ZoneVolume) takes into account the
capacitance of the zone air only. Typically a value 5 times the default
is appropriate to include the capacitance of the room furnishings.
Regards,
David
On 11/18/2010 05:14, Tran Thanh Vu wrote:
Hi everyone
I'm trying to simulate zone and cooling coil with external load
profile by using type 690, but I have difficult when deciding zone
capacitance. May someone give me some instruction to calculate this value.
Thank in advance