Abdulhameed,The most flexible way of including lighting in Type56 is to define a new GAIN in your zone. The gain can be set as a constant value, a scheduled value, or as an input. If you set it as an input then you can pass whatever value you like into the building. The heat gain from the lighting might come from an equation. The complexity will come from the controls. The controls may be other equations or another component. The TESS Green Building library contains a number of lighting control Types that might be of some interest.
Regards, David On 11/8/2010 13:06, Abdulhameed Mambo wrote:
Dear Trnsys users, I have trynsys 17 installed. I read in a journal article that in trnsys there exist an electric ligthing (10 lamps, 0-1000 lux, 800W total), pls what type is that and how do I include it in a building model type 56. I am working on lighting controls in a multi-zone building. Regards. Mambo Abdulhameed Danjuma PhD Research Student, Building Energy Research Group, Department of Civil& Building Engineering, Loughborough University, Loughborough, Leicestershire, LE11 3TU United Kingdom. Mobile: +447780144150 http://www.lboro.ac.uk/departments/cv/staff/students/321.html _______________________________________________ TRNSYS-users mailing list TRNSYS-users@cae.wisc.edu https://www-old.cae.wisc.edu/mailman/listinfo/trnsys-users