Knut Erik,
  Very interesting. I would think that the data-file format would also have had to change since I imagine that the device would require different fractions of full load power as the compressor speed modulates.
Best,
 David


knut.erik.enerstvedt@niva.no wrote:

Mavi and David,

A heat pump with a variable speed compressor can fix the outlet temperature, but they are not very common yet. I once thought I had to model such a heat pump, so I made some modifications to Type 668 water-water heat pump to include a set point on outlet load temperature, similar to Type 666 water cooled chiller which has a set point temperature on the chilled water stream. It was hard to find data on part load performance, however. Later I found out that I did not need this model after all.

Mavi, let me know if you need more information about the modified heat pump component.


Best regards,
Knut Erik Enerstvedt
 

>Mavi,
> Heat pumps can't really do that - they are either on and operating at whatever capacity they have available given the entering water >conditions or they are off. Unless they are multistage heat pumps, they can't load follow and provide a constant outlet temperature >regardless of the inlet temperature. In reality and in simulation, you would have to look for a method of actually doing that. One thing >you could try is to have a bypass valve upstream of the heat pump, oversize the heat pump so that it can always heat or cool the >liquid enough and then divert some of the upstream liquid around the heat pump and mix it back in downstream like a tempering >valve.
>Best,
> David


>Mavi Cambronero Vázquez wrote:

>Hi everybody!!
 
>I´d like to get a fixed outlet temperature from a water-water heat pump. Do you know how to do it???
 
>Thank you!!!
------------------------------------------------------------------------------------------------------------
Meld deg på vårt nyhetsbrev på
www.niva.no

-- 
***********************************************************************
Thermal Energy System Specialists (TESS), LLC 
David BRADLEY                      22 N. Carroll Street - Suite 370 
Partner                            Madison, WI 53703 
                                   USA
P: +1.608.274.2577 
F: +1.608.278.1475
E-mail: bradley@tess-inc.com 
Web Pages:  http://www.tess-inc.com    and      http://www.trnsys.com

***********************************************************************