Dear Kent,
To model dehumidifcation you need to use the cooling manager, and not
the heating one.
By setting 100% in heating (and thus in humidification) you force TRnsys
to add humidity to your local.
If you want 60% (no more, no less) during occupation, you have to set
the things like this:
inoccupation:
heating: X°C, 0%
cooling: X°C, 100%
Occupation:
heating: Y°C, 60%
cooling: Y°C, 60%
Happy new year to every TRNSYS users.