Re: [TRNSYS-users] Type8a: Setback temperature issue
Thanks Kent,
I do appear to be seeing the same behaviour. Is there a prefered method for reporting such issues?
I was looking for details of Type 671 but dont seem to be able to find any on the TESS /TRNSYS site. Do you have a reference?
Paul
--- On Mon, 7/12/09, Kent Beason <kbeason@schlitterbahn.com> wrote:
> From: Kent Beason <kbeason@schlitterbahn.com>
> Subject: RE: [TRNSYS-users] Type8a: Setback temperature issue
> To: "PAUL COALES" <coalespr@btinternet.com>, trnsys-users@cae.wisc.edu
> Date: Monday, 7 December, 2009, 18:56
> Paul,
>
> I recently had the same problem with Type8a. Related
> to your #2 conditions below, set your "Heating set back
> temperature difference" to zero and see if the heating stage
> operates then. My experience with 8a says it will
> work, but of course with a useless setback function. I
> ended up throwing out Type 8a in my simulation and easily
> using Type 671 from the TESS library.
>
> Kent Beason
> Schlitterbahn Development Group
> 830-609-8904 m
>
> -----Original Message-----
> From: PAUL COALES [mailto:coalespr@btinternet.com]
>
> Sent: Monday, December 07, 2009 7:29 AM
> To: trnsys-users@cae.wisc.edu
> Subject: [TRNSYS-users] Type8a: Setback temperature issue
>
> Hi
>
> Are there any issues with Type8a, setback function? The
> instructions for use seem straight forward but it does not
> seem to work for me:
>
> 1) If INPUT "Set back control function" is fixed at 0,
> setback behaviour is disabled. "Control signal for 1st
> stage heating" is set when "Room temperature" drops below
> "1st stage heating temperature". This behaviour seems
> correct.
>
> 2)If INPUT "Set back control function" is fixed at 1,
> setback behaviour should be enabled. However, the "Control
> signal for 1st stage heating " is never set. My heating
> system never turns on and my room temperature continues to
> fall.
>
> I've set "minimum primary source temperature" to a low
> value (10 degrees) "1st stage heating in 2nd stage" is set
> to 1. "Heating set back temperature difference" is set to
> 1 deltaC
>
>
> Have I missed something?
>
> Paul
>
>
>
>
>
>