Dear Paul
Internal calculation is not ok for back surface of external wall.
You most also choose "userdefined" calculation for that
Wall.
Best regards
Je serai absent du 04
Décembre 2009 au 04 Janvier 2010
I will be absent from 04th December 2009 to 04th January 2010
www.itf.biz
|
Adrien
JEZEQUEL
Simulations Thermiques Dynamiques |
ITF
|
62, Rue du
Bolliet
73230 St Alban Leysse
FRANCE
|
Phone :
Fax :
Mail:
|
+33(0) 479 750
029
+33(0) 479 852 122
a.jezequel@itf.biz |
Afin de contribuer au
respect de l'environnement, merci de n'imprimer cet e-mail que si
nécessaire
Please, consider our
environmental responsability before printing this email
PAUL COALES a écrit :
Hi Adrien,
I select "internal calculation" for "Convective Heat Transfer
Coefficient of Wall" for all my wall types; back and front. Is this
wrong?
Kind Regards
Paul
--- On Mon, 23/11/09, Adrien JEZEQUEL - ITF <a.jezequel@itf.biz>
wrote:
From: Adrien JEZEQUEL - ITF <a.jezequel@itf.biz>
Subject: Re: [TRNSYS-users] Type56a: Automatic Heat Transfer
Calculation Error
To: "PAUL COALES" <coalespr@btinternet.com>
Cc: trnsys-users@cae.wisc.edu
Date: Monday, 23 November, 2009, 8:27
Dear Paul
Your issue concerns Convective Heat Transfer Coefficient of wall in wall type manager.
You certainly select an internal calculation for an external wall in
your bui file, instead of userdefined.
Message error indicates that automatic heat transfer calculation is
only allowed on surface within a zone.
Best regards
Je serai absent du 04
Décembre 2009 au 04 Janvier 2010
I will be absent from 04th December 2009 to 04th January 2010
www.itf.biz
|
Adrien
JEZEQUEL
Simulations Thermiques Dynamiques |
ITF
|
62,
Rue du
Bolliet
73230 St Alban Leysse
FRANCE
|
Phone :
Fax :
Mail:
|
+33(0) 479 750
029
+33(0) 479 852 122
a.jezequel@itf.biz |
Afin de
contribuer au
respect de l'environnement, merci de n'imprimer cet e-mail que si
nécessaire
Please,
consider our
environmental responsability before printing this email
PAUL COALES a écrit :
Hi All
I have an error reported on a simulation run and need some suggestions as to what could be going wrong.
Fatal error at time 0.00
Generated by unit 3
Generated by Type56a
Message Error in automatic heat transfer calcualtation for surface 7 or it's adjacent surface. Automatic heat transfer calculation is only allowed on surface within a zone. Please check input file .bui
This is different to the example posted erlier in the year. I am modeling underfloor heating here.
I tried deleting the surface 7 but this does not change the report. I still refers to surface 7.
Any clues? I can forward the .bui file if interested.
Kind Regards
Paul