[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

Re: [TRNSYS-users] 24h mean value of operative room temperature



If you're in a hurry for the running average model, there's one available in the individual components section of the TESS Libraries for TRNSYS (www.trnsys.com).

Jeff

Jeff Thornton
President - TESS, LLC

22 North Carroll Street - Suite 370
Madison WI 53703 USA

Phone: 608-274-2577
Fax: 608-278-1475
E-mail: thornton@tess-inc.com
Web: www.tess-inc.com







----- Original Message -----

From: "David Bradley" <bradley@tess-inc.com>
Sent: Fri, October 2, 2009 9:15
Subject: Re: [TRNSYS-users] 24h mean value of operative room temperature

Type55 will generate the mean value over a 24 hour period (for example midnight to midnight) and then reset at the end of that period. If your controls are based on what the previous day's mean operative temperature was, you can do it with Type55. If, on the other hand, you want to control based on a running average over the past 24 hours, you'd have to use a different Type. A running average component will be included in TRNSYS 17.
Regards,
 David

P. Demircian wrote:

hello .. ,

I want to use the 24h mean value of my operative room temperature too control my cooling system (Active Layer), The problem is that i have no clue how too do this, I am using Trnsys 16 Studio and try it with TYPE 55..has any one a clue how to do it. 

 

Best Regards Petros

 

Mit freundlichen Grüßen

 

P.Demircian

 

fischer  •  energie  +  tga consult 

Ingenieurgesellschaft mbH

Dieselstraße 18
61191 Rosbach
Telefon: 06003 – 93504-0
Telefax: 06003 – 93504-22


E-Mail:
p.demircian@fIscher-tgaconsult.de

 


_______________________________________________ TRNSYS-users mailing list TRNSYS-users@cae.wisc.edu https://www-old.cae.wisc.edu/mailman/listinfo/trnsys-users

-- 
***********************************************************************
Thermal Energy System Specialists (TESS), LLC 
David BRADLEY                      22 N. Carroll Street - Suite 370 
Partner                            Madison, WI 53703 
                                   USA
P: +1.608.274.2577 
F: +1.608.278.1475
E-mail: bradley@tess-inc.com 
Web Pages:  http://www.tess-inc.com    and      http://www.trnsys.com

***********************************************************************

_______________________________________________
TRNSYS-users mailing list
TRNSYS-users@cae.wisc.edu
https://www-old.cae.wisc.edu/mailman/listinfo/trnsys-users